Model Specific Specifications
  I-500 I-800 I-1100 I-1500
Volt Amps 500 800 1100 1500
Watts 310 500 710 1000
Number of Output Receptacles 4 4 6 6
Number of Switched Outlet Pairs 2 2 3 3
Runtime at Full Load 5 min 5 min 5 min 6 min
Runtime at Half Load 15 min 15 min 15 min 18 min
Physical Dimensions 5.5" x 16.75" x 7.75" 7.75" x 17.75" x 8"
Shipping Dimensions 10.25" x 20.5" x 12.5" 12" x 22" x 13"
Physical Weight 26 33 48 54
Shipping Weight 30 37 54 59


General Specifications
Voltage Regulation Front / Back Panel
100 Volt Mode Boost Range 97 - 89 VAC Load Graph 5 lights
110 Volt Mode Boost Range 100 - 91 VAC Battery Graph 5 lights
115 Volt Mode Boost Range 103 - 93 VAC Battery Fault Indicator Light
120 Volt Mode Boost Range 108 - 96 VAC On Battery Indicator Light
100 Volt Mode Buck Range 129 - 141 VAC UPS Fault Indicator Light and Audible Alarm
110 Volt Mode Buck Range 132 - 145 VAC Test / Silence Button Light
115 Volt Mode Buck Range 135 - 148 VAC Site Wiring Fault Indicator Light (On 120V Models Only)
120 Volt Mode Buck Range 138 - 151 VAC Boost Indicator Light
Buck / Boost Percentage "10% Meets 1996 CBEMA Voltage Regulation Standards Buck Indicator Light
  Overload Indicaor Light and Audible Alarm
Input/Output Short Circuit Indicator Multiple Lights and Audible Alarm
Normal Input voltage 89-151 VAC General Fault Indicator All Lights and Audible Alarm
Normal Input Frequency Autoselecting "5% AC Acceptable Indicator Light
Input Protection Circuit Breaker Active Outlet Diagram 4 lights
Output Voltage 100/110/120  
Short Circuit Protection Inverter & AC Modes Power Management
Overload Shutdown Over 110% Shutdown in XX Minutes Port Type RS-232
Output Waveform Sine Wave Intelligent Card Slot Available on 1100 and 1500 VA Models Only
Total Harmonic Distortion Less than 3% Remote Modem Slot Available on 1100 and 1500 VA Models Only
  SNMP Card Available
Surge Suppression Windows Plug & Play Yes
IEEE Cat. C NM: 170V
CM: 230V
 
Software Configurable Features
Joules / Peak KAmps 2070 / 59 KA Boost Transfer Voltage Software Selectable
Net / Fax / Modem Connector Type RJ-45 Buck Transfer Voltage Software Selectable
Suppression Components 6 MOVs, 3 Avalanche Diodes, Gas Tube Duration of Low Battery Warning 2, 5, 7 or 10 minutes
  UPS Shutdown Delay 20, 180, 300 or 600 seconds
Noise Rejection Load Shed Delay by Outlet Pair Disable pair in 3, 6 or 9 minutes
Normal Mode 100 KHz 80 dB Auto Start Select Auto Start (default) or manual start after AC restore
Normal Mode 1 MHz 65 dB Silence Alarm Options 5 (default) or 30 second delay, low battery, no alarm
Normal Mode 10 MHz 35 dB Self Test Scheduling Options Power On and 7 day (default), POST, 7 day, None
Common Mode 100 KHz 45 dB UPS Identification Up to 7 Characters
Common Mode 1 MHz 48 dB Noise Sensitivity Select Normal (default), reduced or low
Common Mode 10 MHz 50 dB Remote Switching by Outlet Pair Immediate turn On, Off or Reboot
Filtering Components Torroid, Capacitors  
  Enviroment / Warranty
UPS Temperature 0 - 40 C
Transfer in msec 2-4 milliseconds Humidity 5-90% (non-condensing)
Hot-Swap Batteries Yes Audible Noise @1M
(500 & 800 VA)
40 dB
Recharge time to 90% less than 6 hours Audible Noise @1M
(11 & 1500 VA)
45 dB
UPS Self-Test Cycle Default: Every 7 days
(User Programmable)
Agency Approvals CE, VDE, CISPR, UL, TUV, CSA, FCC, ISO 9002
Battery Self-Test Cycle Power On & Continuous Warranty 5 years